Inspection |
1. |
Measure the pressure of high pressure line by measuring voltage output between NO.1 and NO.2 terminals. |
2. |
Inspect the voltage value whether it is sufficient to be regular value or not.
|
3. |
If the measured voltage value is not specification, replace the A/C pressure transducer. |
Replacement |
1. |
Disconnect the negative (-) battery terminal. |
2. |
Recover the refrigerant with a recovery/charging station. |
3. |
Disconnect the A/C pressure transducer connector (3P) (A).
|
4. |
Installation is the reverse order of removal. |
Description A/C pressure transducer convert the pressure value of high pressure line into voltage value after measure it. By converted voltage value, engine ECU controls cooling fan by operating it high ...
Description 1. The photo sensor is located at the right of defrost nozzle. 2. The photo sensor contains a photovoltaic (sensitive to sunlight) diode. The solar radiation received by its light receiving ...
Inspection 1. Ignition "OFF" 2. Disconnect evaporator temperature sensor. 3. Using the multi-tester, Measure resistance between terminal "1" and "2" of evaporator temperature sensor. Specification Evaporator coretemperature[°C(°F)]Resistance[K?]-10 / (14)43.350 / (32)27.6210 / (50)18.0720 / (68)12.1130 ...
Replacement 1. Discharge refrigerant from refrigeration system. 2. Replace faulty tube or hose. Cap the open fittings immediately to keep moisture or dirt out of the system. 3. Tighten joint of bolt or nut to specified torque. Connections should not be torque tighter than ...